One (1) point is awarded where project teams demonstrate that internal ambient noise levels in the nominated area are no more than 5dB(A) above the lower figure.
The noise measurement and documentation must be provided by a qualified acoustic consultant and in accordance with AS/NZS 2107:2016. Noise measurement must account for all internal and external noise including noise arising from building services equipment, noise emission from outdoor sources such as traffic, and (where known) noise from industrial process. Occupancy noise is excluded.
Compliance shall be demonstrated through measurement, and the measurements shall be conducted in at least 10% of the spaces in the nominated area. The selection of representative spaces must be justified within the Submission Template and must consider how the spaces are considered to be the most conservative with respect to both internal, and external noise sources.
The range of measurement locations shall be representative of all spaces available within the nominated area. All relevant building systems must be in operation at the time of measurement. Projects less than 500m2 Gross Floor Area (GFA) must account for measurements conducted in at least 95% of spaces within the nominated area.
Provisions for Naturally Ventilated Buildings
In naturally ventilated buildings, all measurements must be carried out with natural ventilation openings in the open position. The internal ambient noise levels must be no more than 10dB(A) above the lower figure.
Provisions for Mixed Mode Buildings
For purposes of this credit, mixed mode buildings can be treated as mechanically ventilated.