One (1) point is awarded where project teams demonstrate that the ventilation system meets all of the following conditions:
-
The entry of outdoor air pollutants is mitigated, in accordance with 9.1.1;
-
The system is designed for ease of maintenance and cleaning, in accordance with 9.1.2; and
-
The system has been cleaned prior to occupation and use, in accordance with 9.1.3.
9.1.1 Entry of Outdoor Pollutants
The entry of outdoor air pollutants to the space must be minimised. The building ventilation systems must be designed to comply with ASHRAE Standard 62.1:2013 in regards to minimum separation distances between pollution sources and outdoor air intakes. Windows, doors, openings, vents, grilles, and skylights are all considered outdoor air intakes for purposes of this credit and must be modelled taking into account their free area.
Compliance is to be demonstrated in accordance with the distances specified in Table 5.5.1 of the Standard, however projects must also ensure compliance with any other requirement or guidance nominated within the Standard. Analytical solutions are also acceptable by following the example provided within Appendix F of ASHRAE Standard 62.1.
9.1.2 Design for Ease of Maintenance and Cleaning
Any mechanical ventilation system within the building, whether existing or new, must be designed to provide adequate access for maintenance, to both sides of all moisture and debris-catching components, within the air distribution system. Moisture-producing and debris-catching components include items such as cooling coils, heating coils, fan coil units, humidifiers and filters in the air handling system.
Where components do not have access for maintenance from both sides due to the size of the unit, project teams are encouraged to submit a technical question to the GBCA outlining how maintenance and cleaning processes of the air distribution systems components are achieved in line with the intent of the criterion.